Conduit fill calculator
NEC 2023 Chapter 9 tablesAdd the conductors in a run of EMT, IMC, RMC or PVC and see the fill from NFPA 70 (NEC) 2023 Chapter 9: Table 5 for each wire’s area, Table 4 for the raceway, and Table 1 for the allowed percent. Mixed sizes are allowed. The calculation stays in this tab.
Fill in the fields to see the result.
How to use it
- Pick the conduit or tubing type and either a trade size or “smallest size that fits”.
- Enter conductors one per line, for example 3 x 12 AWG THHN. If you leave the insulation off, THHN/THWN is used.
- Read the fill percent against Table 1, and the next listed size if this one is over the limit. Switch to metric to see square millimetres and the metric designator.
How the fill is worked out
Each conductor’s approximate cross-section comes from Chapter 9 Table 5 for its size and insulation (THHN/THWN/THWN-2, XHHW/XHHW-2, TW/THW, or RHH/RHW/RHW-2 without an outer covering). The areas are added. The raceway’s internal area is the 100% column of Table 4 for that type and trade size. Fill percent is (total conductor area) ÷ (Table 4 area) × 100.
Table 1 then sets the cap: 53% when there is one conductor, 31% when there are two, and 40% when there are more than two. A short nipple (24 in or 600 mm or less) may use 60%, which is a Chapter 9 note, not a general permission for a long run. This page compares the sum with those percentages and does not use the pre-rounded 40% columns, so a mixed-size pull stays consistent.
Annex C is a lookup of how many conductors of one size fit. It should agree with this method for a single size, but Annex C is not a substitute when you mix sizes — that is what Tables 1, 4 and 5 are for. Always confirm the edition your Authority Having Jurisdiction has adopted, and the manufacturer’s dimensions when the fill is close to the limit.
Worked example
Six 4 AWG THHN conductors: Table 5 lists 0.0824 in² each, so the total is 6 × 0.0824 = 0.4944 in². More than two conductors means a 40% cap, so the raceway must have at least 0.4944 ÷ 0.40 = 1.236 in² of internal area. 1 in EMT is 0.864 in² in Table 4, which is short of 1.236 in². 1¼ in EMT is 1.496 in², and 40% of that is 0.5984 in², which covers 0.4944 in². The fill is 0.4944 ÷ 1.496 ≈ 33.05%. Annex C Table C.1 allows seven 4 AWG THHN in 1¼ in EMT, so six is within that lookup as well.
Details
- Table 1 allowed fill
- 53% for one conductor, 31% for two, 40% for more than two. A nipple 24 in (600 mm) or shorter may use 60% (Chapter 9 notes to the tables).
- Tables used
- Chapter 9 Table 4 (100% internal area) and Table 5 (insulated conductor area). Compact conductors (Table 5A) are not listed.
- Conduit types
- EMT (Art. 358), IMC (Art. 342), RMC (Art. 344), rigid PVC Schedule 40 and 80 (Art. 352). EMT has no 5 in or 6 in row in the 2023 table.
- Source
- NFPA 70, National Electrical Code, 2023 edition, Chapter 9, Tables 1, 4 and 5. Verify with the edition your AHJ has adopted.
Questions
Does this replace the NEC or a permit review?
No. The figures are transcribed from the 2023 Chapter 9 tables and the math is the Chapter 9 method, but your installation has to follow the code edition your AHJ has adopted, any local amendments, and the conductor manufacturer’s data. Treat the result as a check, not an approval.
Can I mix wire sizes and insulations?
Yes. That is the point of using Tables 1, 4 and 5 instead of Annex C. Enter each group on its own line, for example 3 x 12 AWG THHN and 1 x 12 AWG THHN, or 4 x 10 AWG XHHW.
Why might this disagree with Annex C by one conductor?
Annex C counts identical conductors and already applies Table 1, including the 53% rule for a single large conductor. This page uses the same rules. A difference of one usually means a different edition, a compact conductor (Table 5A, not used here), or a rounded 40% column used instead of the 100% area. If the fill is close to the cap, check the printed tables.
What is not included?
Compact-stranded conductors (Table 5A), cables (Chapter 9, Note 9 and the cable articles), flexible metal conduit, ENT, and any jacket or pulling compound. Ampacity and derating are a different calculation (Article 310), not fill.
Is what I type sent anywhere?
No. The calculation runs in this browser tab with the same code our MCP server uses. Nothing you type is sent to a server or saved, apart from settings like filing status, which stay in this browser.
Can an AI agent use this?
Yes. The same function is a tool on our free MCP server at tools.cuelark.com/mcp, so ChatGPT, Claude or Cursor get exactly the answer this page shows. 'Copy MCP call' gives you the arguments.